Description
The shear strength of unreinforced masonry
construction depends largely on the strength of the mortar used in the wall. An
in-place shear test is the preferred method for determining the strength of
existing mortar. The results of these tests are used to determine the shear
strength of the wall.
Equipment
·
Chisels and grinders are needed to remove the bricks and mortar
adjacent to the test area.
·
A hydraulic ram, calibrated and capable of displaying the applied load.
·
A dial gauge, calibrated to 0.001 inch.
Execution
Prepare the test location by removing the brick,
including the mortar, on one side of the brick to be tested. The head joint on
the opposite side of the brick to be tested is also removed. Care must be
exercised so that the mortar joint above or below the brick to be tested is not
damaged.
The hydraulic ram is inserted in the space where
the brick was removed. A steel loading block is placed between the ram and the
brick to be tested so that the ram will distribute its load over the end face
of the brick. The dial gauge can also be inserted in the space.
The brick is then loaded with the ram until the
first indication of cracking or movement of the brick. The ram force and
associated deflection on the dial gage are recorded to develop a
force-deflection plot on which the first cracking or movement should be
indicated. A dial gauge can be used to calculate a rough estimate of shear
stiffness.
Inspect the collar joint and estimate the
percentage of the collar joint that was effective in resisting the force from
the ram. The brick that was removed should then be replaced and the joints
repointed.
Personnel
Qualifications
The
technician conducting this test should have previous experience with the
technique and should be familiar with the operation of the equipment. Having a
second technician at the site is useful for recording the data and watching for
the first indication of cracking or movement. The structural engineer or
designee should choose test locations that provide a representative sampling of
conditions.
Reporting
Results
The
personnel conducting the tests should provide a written report of the findings
to the evaluating engineer. The results for the in-place shear tests should
contain, at a minimum, the following information for each test location:
·
Describe
test location or give the identification number provided by the engineer.
·
Specify
the length and width of the brick that was tested, and its cross-sectional
area.
·
Give
the maximum mortar strength value measured during the test, in terms of force
and stress.
·
Estimate
the effective area of the bond between the brick and the grout at the collar
joint.
·
Record
the deflection of the brick at the point of peak applied force.
·
Record
the date of the test.
·
List
the responsible engineer overseeing the test and the name of the company
conducting the test.
Limitations
This
test procedure is only capable of measuring the shear strength of the mortar in
the outer wythe of a multi-wythe wall. The engineer should verify that the
exterior wythe being tested is a part of the structural wall, by checking for
the presence of header courses. This test should not be conducted on veneer
wythes.
Test
values from exterior wythes may produce lower values when compared with tests
conducted on inner wythes. The difference can be due to weathering of the
mortar on the exterior wythes. The exterior brick may also have a reduced depth
of mortar for aesthetic purposes.
The
test results can only be qualitatively adjusted to account for the presence of
mortar in the collar joints. If mortar is present in the collar joint, the
engineer or technician conducting the test is not able to discern how much of
that mortar actually resisted the force from the ram.
The
personnel conducting the tests must carefully watch the brick during the test
to accurately determine the ram force at which first cracking or movement
occurs. First cracking or movement indicates the maximum force, and thus the
maximum shear strength. If this peak is missed, the values obtained will be
based only on the sliding friction contribution of the mortar, which will be
less than the bond strength contribution.